Image from Google Jackets

Way out lighting

By: Language: English Series: Building Services ; 9(8) August 1987, 39-40(2)Publication details: 1987Subject(s): Summary: The BRE has recently completed an investigation into escape route lighting provided to enable occupants to evacuate a building quickly and safely when the normal power supply fails. They conducted an experimental study under three different uniform illumination conditions including one approximating to the British Standard recommending a minimum of 0.2 lux on the centre line of the floor of the escape route; results showed that for smoke free conditions the criteria of BS 5266 is reasonable for corridors but higher illuminance is needed for staircases.
Holdings
Item type Current library Call number Copy number Status Barcode
Journal article London Journal article ABS38050 (Browse shelf(Opens below)) 1 Available 8374-1001

The BRE has recently completed an investigation into escape route lighting provided to enable occupants to evacuate a building quickly and safely when the normal power supply fails. They conducted an experimental study under three different uniform illumination conditions including one approximating to the British Standard recommending a minimum of 0.2 lux on the centre line of the floor of the escape route; results showed that for smoke free conditions the criteria of BS 5266 is reasonable for corridors but higher illuminance is needed for staircases.