245 _aWay out lighting
260 _c1987
350 _a0
490 _aBuilding Services
_v9(8) August 1987, 39-40(2)
520 _aThe BRE has recently completed an investigation into escape route lighting provided to enable occupants to evacuate a building quickly and safely when the normal power supply fails. They conducted an experimental study under three different uniform illumination conditions including one approximating to the British Standard recommending a minimum of 0.2 lux on the centre line of the floor of the escape route; results showed that for smoke free conditions the criteria of BS 5266 is reasonable for corridors but higher illuminance is needed for staircases.
650 _aFIRE
650 _aSAFETY
690 _aBUILT ENVIRONMENT-BUILDING STANDARDS